Overview
ATS for automatic generator control system. When commercial power is off, the generator set is automatically started; if a warm-up time is set, the engine will automatically warm up before starting. After the engine starts successfully, if the generator output voltage is normal, the system will switch the load to generator power. If the start fails, the system will generate an appropriate alarm. Parameters: Model KD199-ATS Voltage DC8.0-18V Power 10W Output power single-phase AC220V / three-phase AC380V Oil relay output DC12V 2A Starting relay output DC12V 2A Preheating relay output DC12V 2A Connect B ON/OFF Operating conditions -20-50°C humidity 20-90% Storage conditions -30-70°C humidity 20-90% Protection level IP41 Insulation withstand AC1.5KV/1min 1mA Weight 6.5kg PROTECTIONS Generator frequency protection Engine oil pressure protection Engine start failure protection Engine stop failure alarm Generator has no output voltage alarm
Specifications
- Size (mm) 300*400*200